€1,790.32

  • €9.95
  • Delivery Time: 4-5 business days
  • Availability: In Stock
  • Product Condition: new

Description

Safety tests on electrical systems after installation, modification or regular repeat testing can be carried out easily and efficiently with the BENNING IT 130.

Measurement functions:
- Low resistance of protective conductor and equipotential bonding conductor connections (test current: 200 mA with polarity reversal)
- Insulation resistance with test voltage of 50/100/250/500/1000 V
- Line impedance (L-N/L) with voltage drop and short-circuit current
- Loop impedance (L-PE) without FI/RCD tripping and short-circuit current
- Testing of FI/RCD circuit breakers, standard and delayed (S), type AC, A, F, B, B+ with AUTO test, touch voltage, tripping time and tripping current (ramp test)
- TRUE RMS Voltage, Frequency and Phase Direction Testing
- First fault leakage current in the IT network
- Earthing measurement via 3-wire method (optionally available via earthing set)
- TRUE RMS Current via current clamps BENNING CC 1/CC 2/CC 3 (optionally available)
- Illuminance via BENNING Luxmeter Type B (optionally available)

Features:

- NEW: Measured value memory over 4 levels: Object/block/safety/measurement point
- NEW: Bidirectional interfaces (USB/RS 232)
- NEW: Upload of plant structures and download of measured values
- NEW: Integrated real-time clock (measured value with date/time)
- NEW: Clear good/bad indication via green/red LED on test unit and switchable Commander test probe
- NEW: Commander test probe with TEST and MEMORY button and bright LED measuring point illumination
- NEW: Connection for barcode scanner to identify the measuring point and rename the memory location.
- Help function with connection diagram
- Graphic display with background lighting
- Power supply via 6 NiMH-AA rechargeable batteries
- Battery charging function integrated in the device
- Delivery incl. bag, batteries, test leads, charging cable, switchable Commander test probe, PC software and calibration protocol

Protocol software BENNING PC-Win IT 130:
- NEW: Creation and transfer (upload) of plant structures to BENNING IT 130 for rational repeat testing
- Measured value download and logging via test report and ZVEH test report

Technical data:

Display: Graphic display (illuminated)
Low resistance measurement: 0.01 Ohm - 2 kOhm
Insulation resistance: 10 kOhm - 1000 MOhm
Power impendance (L-N/L): 0.01 Ohm - 10 kOhm
Loop impedance (L-PE): 0.01 Ohm - 10 kOhm
Short-circuit current: 0.01 A - 200 kA
FI/RCD test type AC/A/F and B/B+: Tripping time, tripping current (ramp) Touch voltage, auto test
Rotary field: Yes
Voltage (TRUE RMS), frequency: 1 V - 550 V, 0 Hz - 500 Hz
Grounding resistance: 0.01 Ohm - 2,000 Ohm (via grounding set)
Current (TRUE RMS): 0.1 mA - 400 A (via pliers)
Illuminance: 0.01 lux - 20 klux (via sensor)